When the Temperature Controller is used in public applications, it
should be installed where it can not be adjusted by the public (i.e. a
maintenance room or manager’s ofce).
NOTE: The Temperature Controller(s) have default temperature settings for the Rinnai
Water Models. See Controllers Set Pattern page for details.
NOTE: Controllers have to be wired in Parallel. Each Controller can
share the same feeder circuit wire.
Controllers cannot be wired in series.
Bath Controller
Main Controller
Controller Connection in Parallel
RINNAI
42
Rinnai America
FF Models
INSTA L L E R S I NSTA L L AT I O N IN S T R U C T I O N S
Remote Controllers- General
The remote controls for the Rinnai Water Heater allow the customer to control the
functions of the water heater and to diagnose certain fault conditions.
Before installing the remote controllers, determine the most convenient location(s).
When deciding on the best location for the remote controllers, consider the
following items:
1) Place the controllers out of reach of small children.
2) Avoid locations where the controller(s) will become hot (over the stove, near
the oven or a radiant heater).
3) Avoid direct sunlight (The digital display can be difcult to read in direct
sunlight).
4) Avoid areas where the remote controller can be splashed with water, oil,
sauce, etc.
5) The remote controller cables carry low voltage, 12VDC digital.