Rinnai 27 RHFE-750ETR Flue Installation Manual
Measure from socket end of pipe. Cut pipe and discard ‘free’ non socketed end.
Cut end to be left smooth.
Ground excavation is not recommended to meet clearance or space requirements unless
there is sufficient drainage provision.
A small amount of ‘O’ ring lubricant on rubber seals will assist assembly.
j.) Assemble vertical ‘Down’ section of the flue with
the STRAIGHT END of the ESPIPE900 fitted to
the end of the condensate trap.
k.) Fit ESPLATE over vertical 'Down' section to seal
gap in floor. Ensure that the 'Down' section of flue
is centered within the 100 mm hole through floor.
Screw ESPLATE to floor.
l.) Attach ESBENDS beneath floor so the socket
ends face toward the flue terminal. Fit stand off-
clip to secure vertical 'Down' section of pipe in
place.
m.) Secure the socket joints between the condensate
trap, vertical section of ESPIPE900 and the 2
bends. Use a screw or pop rivet to prevent
accidental dislodgement.
n.) Install horizontal 'Out' section of flue using
ESPIPE900 as required. Pipe must be installed
so there is a 2° fall toward the flue terminal.
o.) Fit stand-off clips to secure horizontal sections of
ESPIPE900 in correct location.
p.) Continue until ESPIPE900 emerges from beneath
the house.
Pop rivet(s), self tapping screw(s) are fitted to prevent accidental or erroneous
dislodgement which could result in a dangerous situation. Accidental or erroneous
dislodgement could occur as a result of future servicing the Aspiration heater or as a result
of other activities in the vicinity of the heater or flue system.
Stand off clips support the weight of the flue and also prevent accidental dislodgement.
4. Creating a horizontal flue terminal at the end of a horizontal Co-axial flue pipe
Components
Wall Terminal Kit (ESWTKIT)
Co-axial flue pipe (ESPIPE900)
Method
a.) Ensure location selected complies with the
requirements of AS 5601 Figure 5.3
(Reproduced in Appendix A).
b.) Cut outer length of air supply tube (socket end) so
it protrudes past external wall by 15 mm.
c.) Cut inner flue pipe so it protrudes past the end of
the air supply tube by 25 mm.
d.) Fit inner flue spacer.
e.) Fit Wall plate.
f.) Gently tap in flue grill into small flue pipe.
NOTE
Pop rivet or 12 mm
self tapping screw
IMPORTANT
15mm
25mm
Measure 15 mm between edge
of external wall and edge of
alloy tube. (Not to edge of plastic
spacer)
25 mm between end of alloy
inner and outer tubes to ensure
products of combustion are not
drawn back into air intake.
DOWN & OUT FLUE INSTALLATION