Installation & Servicing Instructions Rinnai Q-Series
15
Minimum required clearances
to combustibles
Minimum required clearances
to non-combustibles
Recommended
service clearances
All types
A
ll types
A
ll types
inch / mm inch / mm inch / mm
Top of boiler 2" / 50 2" / 50 10" / 250
Back of boiler 0" 0" 0
Front of boiler 6" / 150 6" / 150 24" / 600
Left side of boiler 2" / 50 2" / 50 2" / 50
Right side of boiler 2" / 50 2" / 50 0.4" / 10
Floor / Ground 12" / 300 12" / 300 30" / 762
Vent 0" 0" 0"
clearances to the boiler table 3
wall
2"
50
ceiling
Min. 10" /
250mm
15.7"
400
24"
600
service clearances to the boiler gure 5
For closet installation: clearance is 1” / 25mm from the front.
Low Loss Header
Clearances to combustible and non-Combustible is 0 inch for sides, top, front and oor/ground
5.3.2 Clearences from the boiler
2"
50
2" / 50