Installation & Servicing Instructions Rinnai Q-Series
59
- remove and replace the gasket;
Re tting of the components is done in reverse order.
Condensate trap and condensate tray ( gure 31-33) (2 and 4 year maintenance)
Step 1: Condensate trap
- rst remove the condensation cup (7);
Check this for impurities. If there is not a lot of impurities it is not necessary to
clean the condensate tray (Go to Step 3). If there is a lot of impurities in the cup
it is necessary to remove and clean the condensate tray according Step 2;
- remove the inner trap pipe (8) which remains in the condensate tray;
- check the O-rings of the cup as well as those from the pipe and replace if necessary;
- clean both parts by ushing it with clean water;
- grease the O-rings again with acid free O-ring grease to make tting easier;
- if there is a leak at the condensation cup (7) or tray (9) the complete condensate
trap unit (10) has to be replaced by S4451610;
Step 2: Condensate tray
- remove the plug from the ue gas sensor if present;
- turn the two short clamping rods (11 and 12) ¼ turn and remove them by pulling
them forward; Note the correct turning direction (red indicator, g. 33);
- lift the exhaust pipe (13) out of the condensate tray (14);
- press the condensate tray (14) carefully downwards and remove it by pulling it forward;
- replace the gasket between condensate tray and heat exchanger by a new one;
- clean the condensate tray with water and a hard brush;
- check the condensate tray on leaks.
Step 3: Re tting is done in reverse order.
Note that all gaskets seals completely.
Make sure that during re tting the clamping rods they are put in the right
position. They should be turned vertical.
If the boiler should activated with clamping rods in the wrong position it will
cause serious property damage, personal injury or loss of life.
Put the boiler into operation and check the O
2
(see page 51).
If replacement by new gaskets and burner mentioned in this chapter is not done
within the service interval subscribed by Rinnai the boiler can be damaged and
will cause serious property damage, personal injury or loss of life.
Use only original spare parts supplied by Rinnai. If other parts will be used
the boiler can be damaged and will cause serious property damage, personal
injury or loss of life. Use of non-Rinnai parts will result in the void of warranty.
!
DANGER
!
DANGER
11
12
13
14
!
WARNING
Clamping rods gure 33
Condensate tray gure 32
Siphon  gure 31
7
8
9
10